Stairwells Stairs: Metal Walls: Sheetrock, 2 hr fire rated Lighting: Fluorescent,
battery back up
Tenant Finishes Walls: Sheetrock VWC Floors: 30 oz. carpet Ceilings: 2' X 2' grids Doors: 36" X 8'6" mahogany
solid core Lighting: 2' X 4' 18 cell parabolic
LIFE SAFTEY SYSTEMS
Fully sprinklered
Smoke detectors in public areas
Stairwell pressurization
Emergency lights
Diesel fire pump
350 KW emergency generators
Fire standpipe (2-6") risen
Fire command station (1st flr)
Annunciator system
Fire alarm system installed
per NFPA code
SECURITY
Card access
After hours security patrol
Surveillance camera system
HVAC Description of System: 1,500 ton chilled water;
closed loop system
Chillers: 2 - 540 ton Yorks 1 - 420 ton York AHUs 1 per floor
Air Distribution per Floor:
16 zone mixing box
I thermostat per zone for
cooling and heating
Heating: Electric resistance heat
Outside Air:
2,500 cfm/floor
Design Conditions: Summer
Outside: DB 91<F, WB 80<F
Inside: DB 75<F, WB 50<F Winter
Outside: DB 32<F
Inside: DB 78<F
PLUMBING
Dual domestic water pumps
Electric Water heaters (restrooms only)
Waste, vent and water risers
Roof drain system
ELECTRICAL
Main electrical power is fed from 2
sub-stations with auto transfer switch Description Building Power: 480V/ 277V Available: 208/ 110V Chiller Power: 4,160V Emergency Power: 480V/ 277V
DESIGN LIVE LOADS
Live Load Roof 20 lbs PSF Live Load Floor*: 80 lbs PSF Partition: 20 lbs PSF Mechanical Room: 100 lbs PSF Dead Load Floor: 125 lbs PSF